About regular inspections
Update date: April 26, 2021
Maintenance and management of hazardous materials facilities
Owners of all hazardous materials facilities are obligated to maintain the technical standards of their location, structure, and equipment, and must constantly inspect their hazardous materials facilities themselves.
In addition, owners of the hazardous materials facilities listed below are required to conduct periodic inspections, create inspection records, and retain them for a certain period of time . (Although there is no obligation to report to the fire department, you may be asked to submit these materials.)
Targeted hazardous materials facilities | Quantity, etc. of hazardous materials stored or handled |
---|---|
manufacturing plant | Items with a multiple of 10 or more of the specified quantity or an underground tank |
Indoor storage | Multiple of specified quantity is 150 or more |
Outdoor tank storage | The specified quantity is a multiple of 200 or more |
outdoor storage | The specified quantity is 100 or more times |
underground tank storage | all |
mobile tank storage | all |
Refueling office | Those with underground tanks |
Transfer handling office | all |
General handling office | Items with a multiple of 10 or more of the specified quantity or an underground tank |
(Note) The following hazardous materials facilities are excluded:
- Hazardous materials facilities that have safety regulations pursuant to the provisions of Article 19, Paragraph 1 of the Mine Safety Act
- Hazardous materials facilities that have established harm prevention regulations pursuant to the provisions of Article 28, Paragraph 1 of the Explosives Control Law.
- A general handling center where only Class 4 dangerous substances with a multiple of 30 or less of the specified quantity and a flash point of 40 degrees or higher are refilled into containers.
- Among transfer handling facilities, those where the length of piping exceeds 15 km, the maximum normal pressure related to piping is 0.95 MPa or more, and the length of piping is 7 km or more and less than 15 km.
Periodic inspection record sheet
Facility related
Cover (other than loading mobile tank storage) (PDF: 47KB)
Cover (loadable mobile tank storage) (PDF: 44KB)
Please use the above file as a cover and attach the inspection list for each facility and equipment.
Manufacturing site/general handling center (PDF: 8,119KB)
Indoor storage facility (single-storey) (PDF: 85KB)
Indoor storage (other than one-story) (PDF: 86KB)
Indoor storage facility (with multi-use area) (PDF:80KB)
Outdoor tank storage (fixed roof) (PDF: 34KB)
Outdoor tank storage (floating roof) (PDF: 37KB)
Underground tank storage (PDF: 146KB)
Mobile tank storage facility (PDF: 14KB)
Outdoor storage facility (PDF:51KB)
Refueling station (outdoor) (PDF: 199KB)
Fueling station (indoor) (PDF: 214KB)
Fuel service station (outdoor self-service) (PDF: 235KB)
Fuel service station (indoor self-service) (PDF: 243KB)
Transfer handling center (PDF: 277KB)
General handling office (spray painting) (PDF: 212KB)
General handling area (quenching) (PDF: 213KB)
General handling office (filling facility) (PDF: 175KB)
General handling area (refill facility) (PDF: 155KB)
General handling facilities (hydraulic equipment, etc.) (PDF: 223KB)
Equipment related
Indoor (outside) fire hydrant equipment (PDF: 201KB)
Water spray fire extinguishing equipment (PDF: 215KB)
Foam fire extinguishing equipment (PDF: 2,439KB)
Carbon dioxide fire extinguishing equipment (PDF: 139KB)
Halogen fire extinguishing equipment (PDF: 155KB)
Powder fire extinguishing equipment (PDF: 161KB)
Automatic fire alarm equipment (PDF: 41KB)
Cooling water sprinkler equipment (PDF: 277KB)
Water curtain equipment (PDF: 291KB)
Adobe Acrobat Reader DC (formerly Adobe Reader) is required to open PDF files.
If you do not have it, you can download it free of charge from Adobe.
Download Adobe Acrobat Reader DC
Inquiries regarding this page
Inagi City Fire Department Headquarters Prevention Division
2111 Higashi-Naganuma, Inagi-shi, Tokyo (Inagi Fire Department)
Phone: 042-377-7119 Fax: 042-377-0119